eaton corporation ePDU Industrial Products Catalog
2
Option 1
A1
= 120V/15A input, 15A outlets
A2 = 120V/20A input, 20A outlets
B1 = 240V/15A input, 15A outlets
B2 = 240V/20A input, 20A outlets
B3 = 240V/20A input, 15A outlets
C1 = 120V/30A input, 15A outlets
C2 = 120V/30A input, 20A outlets
F1 = 240V/30A input, 15A outlets
F2 = 240V/30A input, 20A outlets
F3 = 240V/30A input, 15A outlets
G1 = 120/240V/30A input, 5-15Rs
H1 = 120/240V/30A input, 6-15Rs
J1 = 120/240V/30A input, 5-15/6-15Rs
Option 2
F
= Filter
N = No Filter
Option 6
09
= 9-foot power cable
15 = 15-foot power cable
Option 5
0
= No current meter
1 = Current meter
Option 4
= Straight blade Plug
L = Locking Plug
Option 3
S
= Straight blade outlets
L = Locking outlets
T982
-
T982 design your own part number guide
Visit www.epdu.com for stock configurations.
-
-
Option 1: Voltage and Current Configuration
See next page
Option 2: EMI/RFI Filtering
Choose “N” for no filtering or “F” for filtering. See Chart 4 (15A/20A units) Chart 5 (30A units) on page 20 filtering specifications.
Option 3: Receptacle Type
Choose either straight blade or twist lock style receptacles. See the table in Option 1 for a view of the available receptacles. Their NEMA designation
number refers to the receptacles.
Option 4: Plug Type
Choose either straight blade or twist lock style plug. See the table in Option 1 for a view of the available plug styles. The NEMA designation number refers
to the plug. Verify you have the correct type of mating receptacle available at your facility. Plug types limit the voltage and current options.
Option 5: Current Meter
This unit is available with or without a front panel digital current reference meter. This two-segment current reference meter will
display the current value of the connected load. (The meter is an AC averaging meter.) This allows you to properly load your PDU
to avoid an overload situation. This can also be used for monitoring to detect a fault before it occurs. The display shows two digits
with no decimal place. The meter is accurate to ±1 amp resolution.
The current meter option is not available on the following
versions: G1 and J1.
Option 6: Power Cable Length
The power distribution unit has either SO, SOOW or SJT type power cable. The length can be specified as 9 feet or 15 feet. The maximum length allowed by
UL standards for an attached power cable is 15 feet. For permanent installations exceeding 15 feet, a licensed electrician should install a permanent circuit.