Toshiba ASD-G9ETH 사용자 설명서

다운로드
페이지 106
 
  
22
ICC 
9.  Parameter Numbering 
Inspection of the Toshiba ASD user’s manual reveals that the ASD’s 
parameters are organized as hexadecimal numbers ranging from F000 to 
FFFF.  These parameters are made accessible to the interface board as 
“registers”, and are numerically remapped to present a more natural interface to 
the communications user.  There are 1500 total registers available via the 
interface board, and their mappings are as shown in Table 1. 
Table 1: ASD Parameter-to-Register Mapping 
Hexadecimal ASD 
Parameter Numbers… 
…Map to Decimal Register 
Numbers 
F000 - F999 
1 - 1000 
FA00 - FA99 
1001 - 1100 
FB00 - FB99 
1101 - 1200 
FC00 - FC99 
1201 - 1300 
FD00 - FD99 
1301 - 1400 
FE00 - FE99 
1401 - 1500 
 
This mapping is easier to understand if one just uses the interface's web page 
as a guide (refer to Figure 6 and section 10.4.4).  The "parameter” numbers 
(ASD references) and "register” numbers (network references) for all available 
parameters are shown in the first two columns.  Commanding the drive over the 
network therefore entails writing to registers 1007 (option board command) and 
1008 (option board frequency command), which correspond to ASD parameters 
FA06 and FA07, respectively. 
 
 
Figure 6: Web Page Register Assignment Reference 
 
To avoid confusion, when this user’s manual uses the term “parameter”, it will 
be referring to the ASD’s hexadecimal number as documented in the ASD