Alliance Laundry Systems 1305 사용자 설명서

다운로드
페이지 111
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
F232120
36
Allen-Bradley 160-Series AC Drives
Allen-Bradley 160-Series AC Drives
Installation/Wiring
Input Power Conditioning
The drive is suitable for direct connection to input 
power within the rated voltage of the drive. Listed in 
Table 21
 
are certain input power conditions which may 
cause component damage or reduction in product life. 
If any of the conditions exist, as described in Table 21,
 
install one of the devices listed under the heading 
Corrective Action on the line side of the drive.
IMPORTANT: Only one device per branch circuit 
is required. It should be mounted closest to the 
branch and sized to handle the total current of the 
branch circuit. 
An incorrectly installed system can result in 
component damage or reduction in product 
life. The most common causes are:
1. Wiring AC line to drive output or control 
terminals.
2. EXTERNAL voltage application to control 
terminals.
3. Incorrect or inadequate AC supply.
Contact factory for assistance with 
application or wiring.
W660
CAUTION
Input Power Condition
Corrective Action
Low Line impedance (less than 1% line reactance)
Install Line Reactor
or Isolation Transformer
or Bus Inductor – 5.5 & 11kW (7.5 & 15 HP) drives 
only
Greater than 120 kVA supply transformer
Line has power factor correction capacitors
Install Line Reactor 
or Isolation Transformer 
Line has frequent power interruptions
Line has intermittent noise spikes in excess of 6000V 
(lightning)
Phase to ground voltage exceeds 125% of normal line to line 
voltage
Remove MOV jumper to ground.
or Install Isolation Transformer with grounded 
secondary
if necessary
Ungrounded distribution system
240V open delta configuration (stinger leg) 
(1)
Install Line Reactor
(1)
 For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase 
that is tapped in the middle to the neutral or earth is referred to as the “stinger leg,” “high leg,” “red leg,” etc. This 
leg should be identified throughout the system with red or orange tape on the wire at each connection point. The 
stinger leg should be connected to the center Phase B on the reactor. 
Table 21