Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–8
Using Intelligent Input Terminals
Terminals [1], [2], [3], [4], and [5] are identical, programmable inputs for general use.
The input circuits can use the inverter’s internal (isolated) +24V field supply (P24) to
power the inputs. The input circuits are internally connected to the power supply ground.
As the diagram shows, you can use a switch (or jumper) to activate an input terminal that
has been configured.
The input circuits can use the inverter’s internal (isolated) +24V field supply (P24) to
power the inputs. The input circuits are internally connected to the power supply ground.
As the diagram shows, you can use a switch (or jumper) to activate an input terminal that
has been configured.
If you use an external supply, its GND terminal must connect to the [L] terminal on the
inverter to complete the input circuit. Current can only flow into each input, so they are
sinking inputs, whether powered internally or externally.
inverter to complete the input circuit. Current can only flow into each input, so they are
sinking inputs, whether powered internally or externally.
NOTE: We recommend using the top row [L] logic GND for logic input circuits and the
[L] GND on the bottom row of terminals for analog I/O circuits.
[L] GND on the bottom row of terminals for analog I/O circuits.
L100 Inverter
Input circuits
1
2
3
4
5
L
P24
+ –
24V
Sinking inputs,
internal supply
L100 Inverter
Input circuits
1
2
3
4
5
L
P24
+ –
24V
Sinking inputs,
external supply
–
+
+
24V