Forward Run/Stop and Reverse Run/Stop Commands:
When you input the Run command via the terminal [FW], the inverter executes the 
Forward Run command (high) or Stop command (low). When you input the Run 
command via the terminal [RV], the inverter executes the Reverse Run command (high) 
or Stop command (low).
NOTE: The parameter F_04, Keypad Run Key Routing, determines whether the single 
Run key issues a Run FWD command or Run REV command. However, it has no effect 
on the [FW] and [RV] input terminal operation.
WARNING: If the power is turned ON and the Run command is already active, the 
motor starts rotation and is dangerous! Before turning power ON, confirm that the Run 
command is not active.
Option
Code
Terminal 
Symbol
Function Name
State
Description
00
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
01
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
Valid for inputs:
C_01, C_02, C_03, C_04, 
C_05
Required settings:
A_02 = 01
Notes:
When the Forward Run and Reverse Run 
commands are active at the same time, the inverter 
enters the Stop Mode.
When a terminal associated with either [FW] or 
[RV] function is configured for normally closed
the motor starts rotation when that terminal is 
disconnected or otherwise has no input voltage.
Example (default input configuration 
shown—see page 
1
2
3
4
5
L
P24
See I/O specs on page 
.
FW
RV