Torque Control Algorithms
The inverter generates the motor output 
according to the V/f algorithm selected. 
Parameter A_44 selects the inverter algorithm 
for generating the frequency output, as shown 
in the diagram to the right. The factory 
default is 00 (constant torque).
Review the following description to help you 
choose the best torque control algorithm for 
your application.
• The built-in V/f curves are oriented toward developing constant torque or variable 
torque characteristics (see graphs below). You can select either constant torque or 
reduced torque V/f control.
Constant and Variable (Reduced) Torque – The graph below (left) shows the constant 
torque characteristic from 0Hz to the base frequency A_03. The voltage remains 
constant for output frequencies higher than the base frequency. The graph below (right) 
shows the general variable (reduced) torque curve. The range from 0Hz to the base 
frequency is the variable characteristic.
Torque Boost – The Constant and 
Variable Torque algorithms feature an 
adjustable torque boost curve. When the 
motor load has a lot of inertia or starting 
friction, you may need to increase the low 
frequency starting torque characteristics 
by boosting the voltage above the normal 
V/f ratio (shown at right). The boost is 
applied from zero to 1/2 the base 
frequency. You set the breakpoint of the 
boost (point A on the graph) by using 
parameters A_42 and A_43. The manual boost is calculated as an addition to the 
standard straight V/f line (constant torque curve).
Be aware that running the motor at a low speed for a long time can cause motor 
overheating. This is particularly true when manual torque boost is ON, or if the motor 
relies on a built-in fan for cooling.
Output
A44
V/f control,
constant torque
V/f control,
variable torque
00
01
Inverter Torque Control Algorithms
Constant torque
A_44 = 00
V
100%
Hz
0
Variable torque
A_44 = 01
V
100%
Hz
0
Base
freq.
Max.
freq.
Base
freq.
Max.
freq.
f base = 
60Hz
Torque boost
A_42 = 11
A_43 = 10 (%)
V
Hz
100%
11.8%
30.0Hz
6.0Hz
A
0