“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–14
Voltage Gain – Using parameter A_45 you can 
modify the voltage gain of the inverter (see 
graph at right). This is specified as a percent-
age of the full scale setting (Automatic Voltage 
Regulation) AVR level in parameter F_03. The 
gain can be set from 50% to 100%. It should be 
adjusted in accordance with the motor specifi-
cations.
The following table shows the methods of 
torque control selection.
A 45
V
100%
50%
Hz
Voltage Gain
0
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
A_41 Torque boost method 
selection
Two options:
00 ...Manual torque boost
01 ...Automatic torque boost
00
00
00
V-Boost  Mode  0
A_42 Manual torque boost 
value
Can boost starting torque 
between 0 and 99% above 
normal V/f curve, from 0 to
1/2 base frequency
11
11
11
V-Boost  code 11
A_43 Manual torque boost 
frequency adjustment
Sets the frequency of the V/f 
breakpoint A in graph (top of 
previous page) for torque boost
10.0
10.0
10.0
%
V-Boost  F 10.0%
A_44 V/f characteristic curve 
selection
Two available V/f curves;
three select codes:
00 ...Constant torque
01 ...Reduced torque
00
00
00
CONTROL      SLV
A_45 V/f gain setting
Sets voltage gain of the 
inverter from 50 to 100%
100
100
100
%
V-Gain      100%