D896 AUTOMATIC VENT DAMPER
68-0186
3
NOTE:
A minimum of a 30 VA transformer must be used
when D896 is installed with S86/S8600/S8610/
S8620.
Electrical Connections:
Four-wire plug receptacle.
Thermostat Anticipator Setting:
0.13A.
Operating  Times:
Approximate Damper Opening Time: 30 seconds.
Approximate Damper Closing Time: 30 seconds.
Temperature Ratings:
Minimum Ambient: 32
°
F (0
°
C).
Maximum Ambient: 150
°
F (66
°
C).
Maximum Furnace Stack: 575
°
F (302
°
C).
Shipping: -20
°
F to +120
°
F (-29
°
C to +49
°
C).
Mounting: See Fig. 2.
Vertical Stack: Any orientation.
Horizontal Stack: The damper actuator must be on the left
or right side of the vent.
IMPORTANT
Do not mount the vent damper with the actuator
above or below the vent.
Dimensions:
See Fig. 1.
DIA
A
DIA
B
DIM.
G
DIM.
H
1    (32)
1
4
2
3
4
DIA
C
4      (116)
9
16
DIM.
D
3     (98)
7
8
7/8 DIA. STD. KNOCKOUT (3) 
(ONE, OPPOSITE SIDE) 
4 (102)
5 (127)
6 (152)
7 (178)
8 (203)
9 (229)
10 (254)
11 (279)
12 (305)
3 15/16 (100)
4 15/16 (125)
5 15/16 (151)
6 15/16 (176)
7 15/16 (202)
8 15/16 (224)
9 15/16 (252)
10 15/16 (278)
11 15/16 (303)
1 9/16 (40)
1 9/16 (40)
1 9/16 (40)
3 3/16 (81)
3 3/16 (81)
3 3/16 (81)
5 3/16 (132)
5 3/16 (132)
5 3/16 (132)
4 1/2 (114)
4 1/2 (114)
4 1/2 (114)
7 1/2 (191)
7 1/2 (191)
7 1/2 (191)
11 1/2 (292)
11 1/2 (292)
11 1/2 (292)
4 (102)
5 (127)
6 (152)
7 (178)
8 (203)
9 (229)
10 (254)
11 (279)
12 (305)
4 1/16 (103)
5 1/16 (129)
6 1/16 (154)
7 1/16 (179)
8 1/16 (205)
9 1/16 (230)
10 1/16 (256)
11 1/16 (281)
12 1/16 (306)
6 (152)
6 (152)
6 (152)
9 (229)
9 (229)
9 (229)
13 (330)
13 (330)
13 (330)
6 3/4 (171)
7 1/4 (184)
7 3/4 (197)
8 1/4 (209)
8 3/4 (222)
9 1/4 (235)
9 3/4 (248)
10 1/4 (260)
10 3/4 (274)
8 7/8 (225)
9 7/8 (251)
10 7/8 (276)
11 7/8 (301)
12 7/8 (327)
13 7/8 (352)
14 7/8 (378)
15 7/8 (403)
16 7/8 (428)
M11381
DIM. F
DIM. E
(70)
BODY SIZE 
(REF)
DIA. A
in. (mm)
DIA. B
in. (mm)
DIA. C 
in. (mm)
DIM. D
in. (mm)
DIM. E
in. (mm)
DIM. F
in. (mm)
DIM. G
in. (mm)
DIM. H
in. (mm)
Approvals:
American Gas Association Certified:
Certificate No. U-66-2A1.
Canadian Gas Association Design Certified:
1029AVD-9081.
Replacement Parts:
Damper Actuator is field replaceable without removing the
damper assembly from the stack.
197516A Wiring Harness is a 4-wire cable, 8 feet (2.5
meters) long, with D896 mating plug on one end and
mating plug for S86/S8600/S8610/S8620 or Penn Baso
G60 or G66 on the other. An outlet box connector is on
each end.
APPLICATION
The D896 Automatic Vent Damper is a 24 Vac, motorized
stack damper. The damper closes off the furnace or boiler
stack during the heating off-cycle. Use the D896 only on
Underwriters Laboratories Inc. listed and American Gas
Association design certified atmospheric type, gas-fired
furnaces and boilers. The furnaces or boilers must be
equipped with a draft hood that has an outlet area no larger
than the damper inlet area. Do 
not use with oil-fired furnace
or boiler, power burner, or direct vent furnace or boiler.
Fig. 1. Installation dimensions in in. (mm).