Honeywell DH90 사용자 설명서

다운로드
페이지 12
For HVAC Installer Only • Installation Guide
equivalent rectangular. For longer lengths, 
use a minimum 12" diameter or equivalent. 
Grills or diffusers on the duct ends must 
not excessively restrict airflow.
•  Isolated Areas: Effective dehumidification 
may require that ducting be branched to 
isolated, stagnant air flow areas. 
Use 8" or larger diameter branch ducting to each 
of two or three areas, use 6" or larger to each of 
four  or  more  areas.  Provisions  must  be  made  to 
provide  airflow  from  supply  locations  to  central 
return location. Proper air distribution is important 
to  ensure  even  humidity  control  throughout  the 
structure.
4.4B Ducting for Fresh Air — Option
Fresh  air  may  be  brought  into  the  structure  by 
connecting  an  insulated  duct  from  outside  the 
structure  to  the  6"  inlet  of  the  DH90.  Advantages 
of this form of ventilation include:
1.  Outside air is filtered before entering the 
building.
2.  Outside air will be dehumidified before 
entering if the DH90 is running in 
dehumidification mode.
3.  Drawing air from outside and blowing 
inside aids in slightly pressurizing the 
structure. This helps prevent dirty and 
humid air from entering elsewhere. 
 
Exhaust fans are recommended in the 
bathrooms and kitchen.
An  insulated  6"  diameter  duct  is  generally 
sufficient  to  provide  up  to  75  CFM  of  outside  air. 
Large  quantities  of  outside  air  will  impact  DH90 
performance  positively  or  negatively,  depending 
upon the inside and outside air conditions. 
The outside air duct should be connected to the 6" 
round collar on the side of the unit. The amount of 
outside air can be restricted by the blade damper 
in  the  6"  collar.  The  actual  amount  of  ventilation 
air  being  delivered  through  the  ventilation  ducts 
must be measured in each installation. Refer to the 
instructions  provided  with  the  W8150  Ventilation 
Control for proper setup instructions.
4.4C Installation in a Basement or Crawl Space 
with an Existing Forced Air HVAC System 
Install a separate 10" return for the DH90 in a central 
area of the structure. Optional: Duct the supply of 
the DH90 to a 10" x 10" x 10" tee/damper, adjusted 
to 20% open to the basement. Duct the other side 
of  the  tee  to  the  air  supply  of  the  existing  HVAC 
system  with  a  backdraft  damper.  Connect  a  duct 
from  outside  to  the  6"  collar  of  the  DH90  if  you 
wish to provide ventilation air. See Figure 2.
Dry air to basement
BASEMENT OR CRAWLSPACE INSTALLATION
Fresh air
Inlet hood
EARD6
motorized
damper
Heating A/C supply air
W8150 Controller
Heating A/C 
return air
Indoor
air return
Figure 2: Basement or crawlspace installation.