DH90 Dehumidifier • For HVAC Installer Only
Instead of installing a separate return to the DH90, 
and  if  the  existing  system  has  multiple  returns, 
it  is  possible  to  select  one  to  disconnect  from 
the  existing  forced  air  system  and  use  it  for  the 
dedicated DH90 return. Always select a return from 
a central location in the structure in an area that is 
always open to the rest of the structure. Do not use 
a return from a room that may have its door closed 
much of the time.
4.4D Installation in an Attic with an Existing 
Forced Air HVAC System
ImPORTANT: ALWAYS install a catch pan 
with a drain or float interrupt for condensate 
under the DH90 in an attic or condensate 
may damage the living space below. 
The interrupt switch should be installed in series 
with  the  field  wire  that  connects  the  blue  lead 
from  the  DH90  to  the  dehumidistat.  If  overflow 
occurs, this switch opens the compressor control 
circuit  and  stops  water  production  before  the 
catch  pan  overflows.  The  DH90  will  continue  to 
ventilate  or  circulate  air  as  normal,  but  will  not 
dehumidify until this switch closes.
The preferred method of installation is to create a 
separate  return  for  the  DH90  in  a  central  area  of 
the  structure.  Duct  the  supply  of  the  DH90  to  the 
air  supply  of  the  existing  HVAC  system.  Connect 
an  insulated  duct  from  outside  to  the  6"  collar  of 
the DH90 if you wish to provide fresh air. Adjust a 
damper in the duct to provide the desired amount 
of fresh air. See Figure 3.
4.4E Installation in a Structure with No Existing 
Forced Air HVAC System 
When installing the DH90 in a structure that does 
not have a forced air HVAC system, a single return 
for  the  DH90  should  be  installed  in  central  open 
area of the structure. 
DO  NOT  locate  the  return  in  a  bathroom  or  a 
kitchen.  The  supplies  of  the  DH90  should  be 
located in the remote areas of the structure (such 
as  bedrooms,  den,  etc.).  By  ducting  this  way,  the 
air  inside  the  structure  will  circulate  through  the 
DH90 to be filtered and dehumidified. 
6" diameter duct is recommended for branches to 
the bedrooms, 8" diameter duct is recommended 
for branches to larger areas. Connect an insulated 
duct from outside to the 6" collar of the DH90 if 
you wish to provide ventilation. See Figure 4.
Fresh air intake
W8150
Controller
Indoor air 
supply
Attic installation
Indoor air
return
Indoor air
return
Supply air 
Heating & A/C unit
EARD6 
Motorized
damper
Figure 3: Attic Installation.