43
Note  
The RF Electronic Thermo-
stat is automatically tested 
when a sensor test begins. 
The panel will announce, 
Sensor XXX activated, sta-
tus is one, if the thermostat 
is OK.
The panel will prompt you to trip each sensor one at a time. You may follow the panel voice 
prompting or test the sensors in any order. Use the “Sensor Tripping Instructions” table on 
the next page to trip sensors.
6.
Interior sirens and speakers sound transmission beeps and a voice announcement 
identifies the tripped sensor. Each beep represents one RF packet. Count the num-
ber of beeps
 and refer to the “Minimum Beeps” table for minimum requirements. 
After the beeps, the panel announces, Sensor Name is activated, sensor status is XX 
(XX = number of RF packets). The system will continue to prompt for sensors that 
have not yet been tested. When all sensors have been tested the panel will 
announce, Sensor test complete, press DONE. 
Note  
If a sensor does not meet 
the minimum transmission 
beep requirements, refer to 
the “If a Sensor Fails the 
Sensor Test” section of this 
manual
Sensor Tripping Instructions
Sensor
Do This
Door/Window
Open the secured door or window
Freeze
Apply ice to the sensor. Do not allow the sensor to 
get wet
Water
Press a wet rag or wet finger over both of the 
round, gold-plated terminals on the underside of 
the sensor
Carbon Monoxide Alarm
Unplug the CO Alarm. Plug it back in, wait 5 sec-
onds, then press the TEST/RESET button until the 
unit beeps 8 times
Glass Guard
Tap the glass 3 or 4 inches from the sensor
Motion Sensor
Avoid the Motion Sensor field of view for 5 minutes, 
then enter its view
Rate-of-Rise Heat Detector
Rub your hands together until warm, then place 
one hand on the detector for 30 seconds
Shock
Tap the glass twice, away from the sensor. Wait at 
least 30 seconds before testing again
Smoke
Press and hold the test button until the system 
sounds transmission beeps
Panic Buttons
Press and hold the appropriate panic button(s) for 
3 seconds
KeyChain Touchpad
Press and hold LOCK and UNLOCK simulta-
neously for 3 seconds
Remote Handheld Touchpad
Press and hold the 2 EMERGENCY buttons simul-
taneously for 3 seconds
2-Way RF Touchpad
Press and hold the 2 EMERGENCY buttons simul-
taneously for 3 seconds
Minimum Beeps
Type of Sensor
Number of Beeps
Wireless Intrusion Sensors
7–8
Wireless Smoke & Heat Sensors
7–8
Wireless Environmental/Panic Buttons
7–8 
Hardwire Loops, RF Thermostat
1
Emergency Buttons (Remote Handheld Touchpads only)
7-8