Panduit Universal Network Zone System 사양 가이드

다운로드
페이지 3
www.panduit.com /networkzone
S P E C I F I C A T I O N   S H E E T
a p p l i c a t i o n s
The Panduit Universal Network Zone System  
is designed to rapidly deploy an industrial Ethernet  
network between the enterprise and plant floor. 
Copper/fiber connectivity and power features  
minimize engineering and installation time resulting in 
faster implementation. The Universal Network Zone 
System provides usability similar to IT switches for 
industrial switches on the plant floor. This ensures 
that management and control of the network does 
not get in the way of making the most effective use of 
available network data.  
With UL Type 4/12/4X, IP66 rating and CE, the 
enclosures provide reliability and high performance, 
as an integral component of the end-to-end solution 
for Industrial Networks. 
s p e c i f i c a t i o n s
The universal network zone system shall include copper/fiber uplinks 
and downlinks optimized for industrial Ethernet switches. System shall 
incorporate redundant power supplies and optional UPS and PoE 
power supply. The enclosure shall be UL 508A, UL Type 4/12/4X, 
IP66 rated and CE. A removable, pre-engineered back plate with DIN 
rails shall be incorporated in the enclosure. Pre-installed accessory 
side panels, fiber slack spool, and L rings shall be included for cable 
management. The door shall be secured with 3mm double bit or slotted 
latch drive feature. The door shall hinge on the right or left. Class 2 power 
circuits shall be pre-wired, labeled, and tested.  A barrier shall be present 
to isolate IT personnel from high voltage power circuit.
Universal Network Zone System
Universal Network Zone System 
See part number table on pages 2-3
Related Products
PanZone 
®  
NEMA 4X Rated
Compression Fittings
Cable diameters 
0.115" – 0.250": 
PZNF1
 
Cable diameters 
0.230" – 0.395": 
PZNF2
 
Cable diameters 
0.170" – 0.450": 
PZNF3
 
Drain kit: 
PZNDVK
IndustrialNet
 TX6
 Connectors 
Category 6  
UTP bulkhead  
connector: 
IAEBH6
 
Category 6  
STP bulkhead  
connector: 
IAEBH6S
Fiber Uplink Accessories 
Surface mount  
fiber box: 
CBXF6BL-AY
 
LC OptiCam
®
 
connector: 
FLCDMCXAQY
 
LC connector 
module: 
CMDSAQLCBL
 
LC OM3 patch cord:  F92ERLNLNSNM001 
Opti-Core
®
 Interlocking  
Armored Cable: 
FOPRX12Y
DIN Rail Patching Accessories
Mini-Com
®
 Copper  
8-Port DIN Rail 
Patch Panel: 
CDPP8RG
 
Mini-Com
®
 Fiber 
8-Port DIN Rail 
Patch Panel: 
FDME8RG
 
Mini-Com
®
 Single 
Port DIN Rail 
Mount Adapter: 
CADIN1IG^
Copper Connectivity
UTP patch cord: 
UTPSP3Y
 
UTP  
Mini-Com 
®
 Jack: 
CJ688TGIW
 
STP patch cord: 
STP6X3IG 
STP  
Mini-Com 
®
 Jack: 
CJS688TGY
TX6500
 Copper Cable
Category 6, UTP: PUR6504BU-UY
Suggested industrial Switches
Cisco^^ IE2000, IE3000, IE4000 series 
switch models
Allen-Bradley* Stratix** 5400, 5700, 8000, 8300 
series switch models
 
^For standard colors other than International 
Gray, replace IG in part number with 
BL (Black), EI (Electric Ivory), IW (Off White), or 
WH (White).
^^Cisco is a registered trademark of Cisco 
Systems, Inc. and/or its affiliates in the United 
States and certain other countries.
*Rockwell Automation and Allen-Bradley are 
registered by Rockwell Automation in the Patent 
and Trademark Office of the United States.
**Stratix is a trademark of Rockwell Automation.
t e c h n i c a l   i n f o r m a t i o n
Standards:
UL 508A Standard for Industrial Control Panels, UL Type 4/12 or 4X, 
IP66 Rated, CE
Dimensions:
Z23U: 36.0"H x 24.0"W x 11.7"D (914mm x 610mm x 297mm)
Z22U: 24.0"H x 24.0"W x 11.7"D (610mm x 610mm x 297mm)
Color and material: 
Enclosures: Gray, 14 gauge cold roll steel or 316 stainless steel 
Back panels: 14 gauge galvannealed steel or 304 stainless steel
Thermal analysis:
Validated to 40°C ambient outside of enclosure or 60°C maximum within  
enclosure at up to 95% (non-condensing) humidity
Installation:
Wall mount with optional outside-mount flange
k e y   f e a t u r e s   a n d   b e n e f i t s 
Switch ready solution: 
Reduces time required for planning, designing, procurement, and  
installation, resulting in simpler specification and up to 75% 
faster implementation
Universal design:
Works with most DIN mount industrial Ethernet switches, providing 
design flexibility
Designed to accept  
customer supplied  
industrial switches: 
Offer management and diagnostics from within IT and controls  
environments to optimize network traffic
Copper/fiber uplinks  
or patch field and  
copper/fiber connectivity:
Enables troubleshooting of network connections and verification of  
field terminations
Included redundant 
power supplies:
Minimize the risk of equipment failure for improved network reliability 
Optional UPS:
Prevents rebooting of switch and loss of network during power outages 
Optional PoE:
Provides 48Vdc  power to the switch for PoE devices to simplify PoE 
capable deployments and save money on the purchase of PoE injectors
Isolation barrier:
Segregates higher line voltage from lower voltage switch for  
increased safety
Bonding provisions and 
grounding bar: 
Ensure path to ground to protect personnel and equipment
Gland plate:
Allows quick and easy access to machine ingress points into enclosure
Detailed 
installation guide:
Provides easy, repeatable design instructions assuring consistency and 
saving time on the job-site