PTM 535Z User Manual  | v1.0 | March 2016 |  Page 9/38 
 
 
PTM 535Z – 2.4 GHZ PUSHBUTTON TRANSMITTER MODULE 
2.5 
Input signals 
 
PTM 535Z data transmits telegrams indicating the status of the following input signals: 
 
 
ECO 200 action direction (press or release) 
Press indicates a move away from the PCB (and the ECO 200 contacts) 
Release indicates a move towards the PCB (and the ECO 200 contacts) 
 
 
On-board meander contact (M1) 
This meander contact is intended for use with a conductive rubber button and is consid-
ered to be active if it is closed. 
Contact EnOcean for reference on suitable rubber contact mats if required. 
 
 
External input signals (IN1 and IN2) 
PTM 535Z provides and internal pull-up resistor on these signals.  
These inputs are considered active if they are connected to Ground (GND). 
  
2.5.1 
PTM 535Z input status encoding 
 
Table 2 below shows the encoding used by PTM 535Z. 
 
 
Input 2 (IN2) 
Input 1 (IN1) 
Meander (M1)  ECO 200 
Command 
0 = Not Connected to GND 
1 = Connected to GND 
0 = Open 
1 = Closed 
Press= Move away from PCB 
Release = Move towards PCB 
0  
Release 
0x23 
Press 
0x22  
Release 
0x12 
Press 
0x13 
Release 
0x14 
Press 
0x15  
Release 
0x16  
Press 
0x17  
Release 
0x18  
Press 
0x19 
Release 
0x1A 
Press 
0x1B 
Release 
0x1C 
Press 
0x1D 
Release 
0x1E 
Press 
0x1F 
 
Table 2:  PTM 535Z input status encoding