wSIM™ FAE WiTry Kit Operation Quick Start Guide
22
c. Click <OK>
d. In the Continue configuring? Window
i. Select the Do not show this dialog again during the current
operation radio button
ii. Click <No>
You should now see wSIM 10001 show up under the Modbus Devices segment
in the System 1® Configuration application.
5. Right click on Modbus Devices >> select Add wSIM >> select wSIM Node
Template
6. In the Properties of wSIM 00000 window
a. Enter the following information on the General Tab
i. User Name: wSIM 10002
ii. Tag Name: wSIM 10002
b. Enter the following information on the Communications Tab
i. Protocol: TCP /IP
ii. Slave Address: 3
iii. Max Data Byte Size: 250
iv. IP Address: 127.0.0.1
v. Port Number: 502
vi. Timeout (Frames): 15000
c. Click <OK>
d. In the Continue configuring? Window
i. Select the “Do not show this dialog again during the current
operation” radio button
ii. Click <No>
You should now see wSIM 10002 show up under the Modbus Devices segment
in the System 1® Configuration application.
in the System 1® Configuration application.
7. Right click on Modbus Devices >> select Add wSIM >> select wSIM Node
Template
8. In the Properties of wSIM 00000 window
a. Enter the following information on the General Tab
i. User Name: wSIM 10003