Operation Quick Start Guide
23
ii. Tag Name: wSIM 10003
b. Enter the following information on the Communications Tab
i. Protocol: TCP /IP
ii. Slave Address: 4
iii. Max Data Byte Size: 250
iv. IP Address: 127.0.0.1
v. Port Number: 502
vi. Timeout (Frames): 15000
c. Click <OK>
d. In the Continue configuring? Window
i. Select the Do not show this dialog again during the current
operation radio button
ii. Click <No>
You should now see wSIM 10003 show up under the Modbus Devices segment
in the System 1® Configuration application.
in the System 1® Configuration application.
9. Right click on Modbus Devices >> select Add wSIM >> select wSIM
Network Statistics
10. In the Properties of wSIM Network Statistics window
a. Leave the defaults on the General Tab.
b. Enter the following information on the Communications Tab
i. Protocol: TCP /IP
ii. Slave Address: 1
iii. Max Data Byte Size: 250
iv. IP Address: 127.0.0.1
v. Port Number: 502
vi. Timeout (Frames): 15000
c. Click <OK>
d. In the Continue configuring? Window
i. Select the Do not show this dialog again during the current
operation radio button
ii. Click <No>