Honeywell International Inc. AZWDGL 사용자 설명서
Installation and Operations Guide
|
Commissioning
© Honeywell
LTBT-TM-AZWIOG
Rev. 0001BETA
13
8.
Set the Device Instance.
9.
Set the ZigBee Network Number. You can use the default setting as
long as it is unique across the BAS. All AZW-5000 devices on a given
network must have the same ZigBee Network Number.
long as it is unique across the BAS. All AZW-5000 devices on a given
network must have the same ZigBee Network Number.
N o t e
You can set up overlapping ZigBee networks as long as you keep
the ZigBee Network Numbers distinct.
10.
Set the MS/TP Network Number. This network number must be unique
within the ZigBee network.
within the ZigBee network.
N o t e
Because each transceiver/controller pair form their own MS/TP
network, the MS/TP Network Number for the coordinator must be
different from the MS/TP Network Numbers of the transceivers.
different from the MS/TP Network Numbers of the transceivers.
11.
If you are commissioning a coordinator, leave the default Baud rate
setting (0=Auto-baud). If you want to specify a Baud rate for a
transceiver, type a rate.
setting (0=Auto-baud). If you want to specify a Baud rate for a
transceiver, type a rate.
12.
Click Commit Configuration Changes and then cycle power to the
device.
device.
N o t e
The display button will no longer open this unit because the
device instance has changed. See “Viewing commissioning data” on
page 21 for instructions on accessing this data.
page 21 for instructions on accessing this data.
13.
Check radio communication. See “Checking radio communication” on
page 16.
page 16.
If it is not functioning properly, see “Troubleshooting weak reception”
on page 22
on page 22
14.
Repeat steps 1 through 13 for each device. You can reuse the
commissioning button because the units ship from the factory with the
device instance set to 9999.
commissioning button because the units ship from the factory with the
device instance set to 9999.