Symptom
Cause and Action
No power available to keypad. 
• Verify adapter is plugged in.
Faulty adapter. 
• Replace adapter.
Dead, low, or no batteries in keypad. 
• Replace the batteries.
Batteries are incorrectly installed. 
• Install batteries as indicated inside the keypad.
Batteries are not making contact with the battery terminals. 
• Adjust the batteries so they make contact with the ter-
minals.
Batteries are low. 
• Replace the batteries.
Keypad is out of system communications range. 
• Move the keypad to within 30 ft. (10m) of an RF Signal
Repeater or RF Processor.
Button being pressed has not been programmed. 
• See the HomeWorks Utility online help for programming
details.
Keypad has not been addressed. 
• See the HomeWorks Utility online help for setup details.
Keypad has an address, but does not have a valid pro-
gramming database. 
• See the HomeWorks Utility online help for programming
details.
LEDs on an adapter-powered keypad do not light.
A battery-powered keypad will not “wake up” when a but-
ton is pressed.
A battery-powered keypad “wakes up” but goes to “sleep”
quickly after a button press.
A battery-powered keypad’s LEDs cycle up and down dur-
ing “wake up”, but the system lights do not respond to but-
ton presses.
Button presses on keypad cause the keypad to quickly
flash all its LEDs simultaneously.
Button presses on keypad cause the keypad to slowly
flash all its LEDs simultaneously.
Troubleshooting Guide
RF Keypads will not control other system devices until the keypads are addressed and programmed. See the
HomeWorks
®
Utility online help.