5.4.2 Measuring reception field strength at location 
of installation
Note
Radio approval
The antenna on the sensor unit is installed at the factory and must 
not be removed.
 
» Contact PRÜFTECHNIK, if you want to use a different type of 
antenna or if you need to extend the original antenna from an 
enclosure with an antenna cable.
Note
Risk of damage to equipment while housing is open!
Touching the electronic components on the mother board can lead 
to electrostatic discharge, which can damage the sensor unit.
 
» If contact with such components cannot be excluded, wear an 
earthing wristband.
•  Adjust the antenna roughly.
•  Open the sensor unit housing by loosening the two screws of 
the cover (size 2.5 Allen screws).
•  Insert the batteries or connect the sensor unit to the 24 V power 
•  Connect a voltmeter to terminals 11 and 12. 
•  Short-circuit terminals 5 and 6 with a wire bridge.
Note
The sensor unit now sends repeat requests for a measuring con-
figuration to the bridge. If the bridge is within the transmission 
range of the sensor unit, it responds by sending a measuring con-
figuration or a test log without data content. By short-circuiting 
terminals 5 and 6, the bridge and the sensor unit remain in perma-
nent communication, and the reception field strength at terminals  
11 and 12 is indicated in the form of a voltage level. 
•  Check the voltage at the eligible locations of installation. Wait for 
approx. 3 – 4 seconds until the reception /voltage has stabilized.
 
U  
> 0.1 V: Reception OK
 U
max. 
= 1.25 V
Installation and commissioning