UTC Fire & Security Americas Corporation Inc 680F-PIR 사용자 설명서
4 / 6
PET Immune SAW PIR Motion Sensors Installation Sheet
Important information Regarding Sensitivity Settings
The sensitivity settings should be set as followed:
Standard Sense:
•
Rooms < 25ft
•
Pets
< 40 pounds
High Sense:
•
Rooms < 35ft
•
Pets
< 20 pounds
Testing
Walk Testing
Walk testing should be done to determine the sensor’s actual
coverage area. The edge of the coverage pattern is
determined by the first flash of the LED. This may change
slightly depending upon the sensitivity setting. Walk test the
unit from both directions to determine the pattern boundaries.
coverage area. The edge of the coverage pattern is
determined by the first flash of the LED. This may change
slightly depending upon the sensitivity setting. Walk test the
unit from both directions to determine the pattern boundaries.
CAUTION: Excessive use of the walk test mode may
reduce battery life. Use only for initial setup and
maintenance testing.
reduce battery life. Use only for initial setup and
maintenance testing.
1. Remove the sensor body from the mounted mounting
plate and then remount the body to activate the 60
second walk test mode.
second walk test mode.
2. Walk across the coverage pattern to determine the
coverage area, indicated by LED activation. Each
activation extends the walk test mode for an additional
60 seconds.
activation extends the walk test mode for an additional
60 seconds.
After 60 seconds without motion the walk test mode and the
LED will no longer activate when motion is detected.
LED will no longer activate when motion is detected.
Note: When the walk test mode has ended, an alarm can be
transmitted only after 3 minutes have passed since the
previous alarm. This 3 minute lockout time reduces
unnecessary RF transmissions in high traffic areas thereby
extending battery life.
transmitted only after 3 minutes have passed since the
previous alarm. This 3 minute lockout time reduces
unnecessary RF transmissions in high traffic areas thereby
extending battery life.
Environment Testing
Turn on all heating or air conditioning sources which would
normally be active during the protection period. Stand away
from the sensor and outside the coverage pattern and watch
for alarms. When testing the Pet Immune PIR also verify the
pets allowed in the coverage pattern do not trip the PIR.
normally be active during the protection period. Stand away
from the sensor and outside the coverage pattern and watch
for alarms. When testing the Pet Immune PIR also verify the
pets allowed in the coverage pattern do not trip the PIR.
Maintenance
At least once a year, the range and coverage should be
verified for proper operation. The end user should be
instructed to put the sensor in walk test mode and walk
through the far end of the coverage pattern to verify proper
detection.
verified for proper operation. The end user should be
instructed to put the sensor in walk test mode and walk
through the far end of the coverage pattern to verify proper
detection.
Replacing the Batteries
When the system indicates the sensor has low batteries,
replace the batteries immediately. The sensors are powered
by the batteries shown in Table 2. Use only the batteries
indicated in Table 2 for the appropriate sensor. See the steps
listed after Table 2 for replacing the batteries.
replace the batteries immediately. The sensors are powered
by the batteries shown in Table 2. Use only the batteries
indicated in Table 2 for the appropriate sensor. See the steps
listed after Table 2 for replacing the batteries.
Table 2: Battery Replacement
60-807-95R
Two AA Alkaline Batteries
60-807-01-95R
One AA Lithium Battery (#60-619).
60-807-02-95R
Two 1.5 AA Lithium Iron Disulfide Batteries (#60-
931).
931).
1. Remove the mounting plate by depressing the button on
the top of the sensor body. With the opposite hand pull
the mounting plate away from the body of the sensor.
See Figure 8.
the mounting plate away from the body of the sensor.
See Figure 8.
2. Remove the PIR cover by depressing the three tabs.
See Figure 8.
3. Remove the old batteries and replace them with new
batteries as noted in Table 2 and Figure 8.
Note: Observe polarity when replacing the batteries. For
all units install the battery on the right side as shown in
Figure 8 with the positive end of the battery facing down
(near the tamper switch). For 60-807-95R and 60-807-
02-95R units with two batteries, install the second
battery on the left side with the positive end of the
battery facing up. See Figure 8.
all units install the battery on the right side as shown in
Figure 8 with the positive end of the battery facing down
(near the tamper switch). For 60-807-95R and 60-807-
02-95R units with two batteries, install the second
battery on the left side with the positive end of the
battery facing up. See Figure 8.
If a battery is installed incorrectly the unit will not function
and the red LED will not light up. The sensor may be
damaged if a battery is installed incorrectly. For sensors
with two batteries, always replace both batteries.
and the red LED will not light up. The sensor may be
damaged if a battery is installed incorrectly. For sensors
with two batteries, always replace both batteries.
4. Dispose of the batteries as required by local
requirements
5. Walk test the PIR to verify proper operation.
Note: When the battery is replaced, wait at least three
minutes after installing the battery before activating the
walk test mode.
minutes after installing the battery before activating the
walk test mode.
Figure 8: PIR Components, Battery Locations & Tamper Switch