PET Immune SAW PIR Motion Sensors Installation Sheet
 
Important information Regarding Sensitivity Settings 
 
The sensitivity settings should be set as followed: 
 
Standard Sense: 
• 
Rooms  < 25ft 
• 
Pets  
< 40 pounds 
High Sense: 
• 
Rooms  < 35ft 
• 
Pets  
< 20 pounds 
Testing 
Walk Testing 
Walk testing should be done to determine the sensor’s actual 
coverage area. The edge of the coverage pattern is 
determined by the first flash of the LED. This may change 
slightly depending upon the sensitivity setting. Walk test the 
unit from both directions to determine the pattern boundaries. 
CAUTION: Excessive use of the walk test mode may 
reduce battery life. Use only for initial setup and 
maintenance testing. 
1.  Remove the sensor body from the mounted mounting 
plate and then remount the body to activate the 60 
second walk test mode. 
2.  Walk across the coverage pattern to determine the 
coverage area, indicated by LED activation. Each 
activation extends the walk test mode for an additional 
60 seconds. 
After 60 seconds without motion the walk test mode and the 
LED will no longer activate when motion is detected. 
Note: When the walk test mode has ended, an alarm can be 
transmitted only after 3 minutes have passed since the 
previous alarm. This 3 minute lockout time reduces 
unnecessary RF transmissions in high traffic areas thereby 
extending battery life. 
Environment Testing 
Turn on all heating or air conditioning sources which would 
normally be active during the protection period. Stand away 
from the sensor and outside the coverage pattern and watch 
for alarms. When testing the Pet Immune PIR also verify the 
pets allowed in the coverage pattern do not trip the PIR. 
Maintenance 
At least once a year, the range and coverage should be 
verified for proper operation. The end user should be 
instructed to put the sensor in walk test mode and walk 
through the far end of the coverage pattern to verify proper 
detection. 
Replacing the Batteries 
When the system indicates the sensor has low batteries, 
replace the batteries immediately. The sensors are powered 
by the batteries shown in Table 2. Use only the batteries 
indicated in Table 2 for the appropriate sensor. See the steps 
listed after Table 2 for replacing the batteries. 
Table 2: Battery Replacement 
60-807-95R 
Two AA Alkaline Batteries 
60-807-01-95R 
One AA Lithium Battery (#60-619). 
60-807-02-95R 
Two 1.5 AA Lithium Iron Disulfide Batteries (#60-
931). 
1.  Remove the mounting plate by depressing the button on 
the top of the sensor body. With the opposite hand pull 
the mounting plate away from the body of the sensor. 
See Figure 8. 
2.  Remove the PIR cover by depressing the three tabs. 
See Figure 8. 
3.  Remove the old batteries and replace them with new 
batteries as noted in Table 2 and Figure 8. 
Note: Observe polarity when replacing the batteries. For 
all units install the battery on the right side as shown in 
Figure 8 with the positive end of the battery facing down 
(near the tamper switch). For 60-807-95R and 60-807-
02-95R units with two batteries, install the second 
battery on the left side with the positive end of the 
battery facing up. See Figure 8.  
If a battery is installed incorrectly the unit will not function 
and the red LED will not light up. The sensor may be 
damaged if a battery is installed incorrectly. For sensors 
with two batteries, always replace both batteries.  
4.  Dispose of the batteries as required by local 
requirements 
5.  Walk test the PIR to verify proper operation.  
Note: When the battery is replaced, wait at least three 
minutes after installing the battery before activating the 
walk test mode. 
Figure 8: PIR Components, Battery Locations & Tamper Switch