X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Load Over Current – This alarm will activate if the load current rises above this
threshold. The alarm will be canceled when the current falls below the cancellation
threshold.
Battery Over Current – This alarm will activate if the magnitude of the battery
Battery Over Current – This alarm will activate if the magnitude of the battery
current rises above this threshold. Thus the alarm will activate either during charge
or discharge if the threshold is exceeded. The alarm will be canceled when the
current falls below the cancellation threshold.
Battery On Discharge – This alarm will activate if the discharge current from the
Battery On Discharge – This alarm will activate if the discharge current from the
battery rises above this threshold. When the discharge current falls below this level
(or the current becomes a charging current) the alarm will be canceled.
13.5.5 - Analog Input Alarms
These are not used in X75.
13.5.6 - Other Alarms
Figure 27 - Alarm Matrix WEB Applet - other alarm settings (typical)
Minimum number of rectifiers – If the number of rectifiers detected in the system
falls below this value then an alarm will be activated. If the number of rectifiers
increases so that it is equal to or above this value then the alarm will be cleared.