waterleakXsystems llc WLXS007 사용자 설명서

다운로드
페이지 36
13 
  Multiple WDUs can be paired with a repeater. 
  Each WDU should only be paired with one repeater. Pairing a WDU with more than one repeater will 
cause simultaneous repeated transmissions and prevent the system from working properly. 
  All WDUs paired with a repeater must be also be paired with the CCU. 
  Non‐primary repeaters only need to be paired with WDUs that require their signals to be 
rebroadcast to the CCU; non‐primary repeaters should not be paired with the CCU or VCU. 
 
 
Solid State Well Relay 
The Solid State Well Relay (WR) can be used with the Basic System WLXS‐007 to turn off a well pump in 
the event of a water leak. This component comes with a white 6' cable with an RJ45 connector on one 
end and three bare end wires on the other end. It should be wired into the facility’s well system 
circuitry, and the low voltage side should then be plugged into the VCU. 
We recommend that a licensed electrician make the required connections to the facility well control 
circuitry to ensure that the installation complies with local codes and regulations.