GT-600/GT-800 Instruction Manual 
73 
 
 
-
 Functional test (L disconnected, PRCD must  
  
trip) 
-
 Functional test (N disconnected, PRCD must  
 trip) 
-
 Non-trip test at I
N/2 
(PRCD must not trip, 
measurement time 300 ms) 
-
 Trip time measurement at I
N 
(PRCD must trip, 
fixed limit value 300 ms) 
-
 Trip time measurement at 5 I
N 
(PRCD must 
trip, fixed limit value 40 ms) 
-
 Trip current measurement 0.5 I
N
 ... I
N
 (11 
steps, duration 300 ms / step, pause duration 
30 ms) 
Timeout (PRCD not activated 
/ deactivated) 
60 s 
Cord R
PE
 compensation 
Yes, via CORD function 
Accuracy of test current I
N/2
 
+0/-10% of I
N/2
 
Accuracy of test current I
N, 
5I
N
 -0/+10% of I
N, 
5I
N
 
Display range trip time 
0 ... 300 ms (I
N
), 0 ... 40 ms (5I
N
Resolution trip time 
0.1 ms 
Accuracy of trip time 
+/- (3% rdg. + 2 ms) 
Max. N conductor resistance 
 
Pre-Tests and Protection,  
Functions and Messages 
Refer to page 64 
 
Protective Extra Low Voltage TRMS (PELV) 
Measurement terminals 
PROBE2 against earth 
Display range 
10.0 ... 150.0 V 
Resolution 0.1 
Limit value 
  Adjustable 10.0 ... 150.0 V, standard values  
 
  25 V and 50 V 
Accuracy 
+/- (2% + 2 V) 
Input resistance 
2.35 M
 
Frequency range 
0 ... 723 Hz 
 
Safety Extra Low Voltage TRMS (SELV) 
Measurement terminals 
PROBE1 against PROBE2 socket 
Display range 
10.0 ... 150.0 V 
Resolution 0.1 
Accuracy 
+/- (2% + 2 V) 
Limit value 
  Adjustable 10.0 ... 150.0 V, standard values  
 
  25 V and 50 V 
Input resistance 
20 M
 
Common mode input voltage 
50 V max. 
Frequency range 
0 ... 723 Hz 
 
AUTO Test measurements (GT-800 only) 
Number of factory-programmed AUTO tests (fixed)  13 
Number of available customer-created AUTO tests 
17