Measuring RCD Tripping Current 
 
apx009f.eps 
Figure 17. RCD Tripping Current/Switch and Terminal Settings 
This test measures the RCD tripping current by applying a test current and then 
gradually increasing the current until the RCD trips. You can use the test leads 
or mains cord for this test. A 3-wire connection is required. 

 Warning 
 
Test the connection between the N-conductor and earth 
before starting the test. A voltage between the N-conductor 
and earth may influence the test. 
 
Leakage currents in the circuit following the residual current 
protection device may influence measurements. 
 
The displayed fault voltage relates to the rated residual 
current of the RCD. 
 
Potential fields of other earthing installations may influence 
the measurement. 
Note 
If the L and N terminals are reversed, the tester will auto-swap them 
internally and continue testing. If the tester is configured for UK 
operation, testing will halt and you will need to determine why the L 
and N are swapped. This condition is indicated by arrows above or 
below the terminal indicator symbol 
()
Type A and type B RCDs do not have the 1000 mA option available. 
To measure RCD tripping current: 
1.  Turn the rotary switch to the I
Δ
N
 position. 
2. Press 
 to select the RCD current rating (10, 30, 100, 300, or 500 mA). If 
the RCD has a special nominal current setting other than the standard