RCD Testing in IT Systems 
RCD testing at locations with IT systems requires a special test procedure 
because the Protective Earth connection is grounded locally and is not tied 
directly to the power system. 
The test is conducted at the electrical panel using probes. Use the connection 
shown in Figure 18 when performing RCD testing on IT electrical systems. 
RCD
Mains S
u
pply
PE (L2/Green)
L (L1/Red)
N
 (L3/Bl
u
e)
 
apx023f.eps 
Figure 18. Connection for RCD Testing on IT Electrical Systems 
The test current flows through the upper side of the RCD, into the L terminal, 
and returns though the PE terminal. 
Measuring Earth Resistance 
(Model 1653B and 1654B Only) 
 
apx010f.eps 
Figure 19. Earth Resistance Display/Switch and Terminal Settings