Function Descriptions
January 07
13
Timing
The shortest polling cycle is 1 second, i.e. signals shorter than 1 second will
generally not be recognized.
The object instances are not automatically queried if the INSYS GSM 4.2 easy is
busy with the following actions:
¾
generally not be recognized.
The object instances are not automatically queried if the INSYS GSM 4.2 easy is
busy with the following actions:
¾
Field strength query and login state query, duration approx. 5s, interval 60s,
may be switched off.
¾
SMS input buffer and processing of SMS, duration approx. 5s, interval 60s, may
be switched off.
¾
Established GSM connection (data connection, DTMF connection, security
callback)
Sending an SMS (fault message, Alive SMS may be switched off, Power up SMS
may be switched off, duration approximately 10 seconds.)
For the values to be monitored applies that all changes must be effective until the
automatic polling is performed again. This applies to most applications (e.g. fill
level monitoring or protective motor switch).
Monitoring with INSYS GSM 4.2 easy is mainly intended for static signals and
values.
If the used signal (e.g. pulse) does not comply with these requirements, this signal
must be directed to an ON or OFF delay or a RS flip-flop in the control program.
may be switched off, duration approximately 10 seconds.)
For the values to be monitored applies that all changes must be effective until the
automatic polling is performed again. This applies to most applications (e.g. fill
level monitoring or protective motor switch).
Monitoring with INSYS GSM 4.2 easy is mainly intended for static signals and
values.
If the used signal (e.g. pulse) does not comply with these requirements, this signal
must be directed to an ON or OFF delay or a RS flip-flop in the control program.
Occurrence of several faults/changes
If several changes occur during a polling interval, the according messages are sent
in the same order in which they were set during the configuration of the INSYS
GSM 4.2 easy. The monitored value 1 is therefore queried prior to the monitored
value 2. If exceeding or changing of values is detected, the system will
immediately attempt to send the alarm message.
If another monitored value changes during the alarm processing, this new alarm
is only detected if the value change lasts until the processing of the previous
alarm is completed. Now the regular polling will restart.
in the same order in which they were set during the configuration of the INSYS
GSM 4.2 easy. The monitored value 1 is therefore queried prior to the monitored
value 2. If exceeding or changing of values is detected, the system will
immediately attempt to send the alarm message.
If another monitored value changes during the alarm processing, this new alarm
is only detected if the value change lasts until the processing of the previous
alarm is completed. Now the regular polling will restart.