Insys GSM EASY 4.1 11-02-01-03-01.027 사용자 설명서

제품 코드
11-02-01-03-01.027
다운로드
페이지 40
INSYS GSM 4.2 easy 
Function Descriptions 
January 07 
15
 
3.3 
Query and Controlling via SMS 
3.3.1  SMS commands 
Many of the INSYS GSM 4.2 easy instances can be configured via SMS (the 
function automatic SMS processing must be activated). It is furthermore possible 
to access the inputs and outputs of the INSYS GSM 4.2 easy indirectly via registers.  
For the INSYS GSM 4.2 easy it is also possible to query various information 
regarding the state of the easy device via SMS, or the control program that is 
running on it. It is also possible to change values of the running program with 
commands. 
Incoming SMS messages are queried once every minute. During this time, no 
polling of the monitored object instances is performed (function "Value 
monitoring"). 
 
All SMS commands must have the following syntax: 
[<password>,]<command>[,CN: <reply>] 
CN means Callback Number 
 
<password>  
Password for remote configuration and SMS query. If no 
password is set, the separating comma is dropped also. No 
space character is permitted between password, comma and 
command. 
<command>   
Command to be executed, with parameters  
<reply> 
 
Optional callback number to which the response  
is sent via SMS. If no reply SMS is desired, the separating 
comma is dropped also. Between command, comma and 
"CN:" no space character is permitted. After "CN:" a space 
character must be entered. 
 
Note: The 
characters 
"
[“, “]""<" and ">" need not be sent. They are 
merely used in the syntax description to indicate the parameters "<" 
and 
">" as well as optional parameters "[and]".