Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 데이터 시트

제품 코드
6ED1057-3BA00-0AA8
다운로드
페이지 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
274
 
Operating Instructions, 06/2014 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/off-delay: Ta 
●  Retentive on-delay: Ta 
●  Wiping relay(pulse output): Ta 
●  Edge triggered wiping relay: Ta 
●  Asynchronous pulse generator: Ta 
●  Stairway light switch: Ta 
●  Multiple function switch: Ta 
●  Stopwatch: AQ 
●  Analog filter: AQ 
●  Average value: AQ 
●  Max/Min: AQ 
●  Threshold trigger: Fre 
You select the required function by the block number. 
Parameter p (number of decimals) 
Parameter p applies only to the display of the Ax value in a message text. 
Description of the function 
The function reads the value of the signal at the analog input Ax.  
This value is multiplied by the value of parameter A (gain). Parameter B (offset) is added to 
the product, as follows:  
(Ax * Gain) + Offset = Actual value Ax 
The function block calculates the proportion of the value Ax to the range. The block sets the 
digital output Q high for the same proportion of the PT (periodic time) parameter, and sets Q 
low for the remainder of the time period. 
Examples with Timing Diagrams 
The following examples show how the PWM instruction modulates a digital output signal 
from the analog input value: 
Example 1 
Analog input value: 500 (range 0 to 1000)  
Periodic time T: 4 seconds 
The digital output of the PWM function is 2 seconds high, 2 seconds low, 2 seconds high, 2 
seconds low and continues in that pattern as long as parameter "En" = high.