5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
275
 
 
 
Example 2 
Analog input value: 300 (range 0 to 1000) 
Periodic time T: 10 seconds 
The digital output of the PWM function is 3 seconds high, 7 seconds low, 3 seconds high, 7 
seconds low and continues in that pattern as long as parameter "En" = high. 
 
Calculation rule 
Q = 1, for (Ax – Min) / (Max – Min) of time period PT 
Q = 0, for PT – [(Ax – Min) / (Max – Min)] of time period PT. 
Note: Ax in this calculation refers to the actual value Ax as calculated using the Gain and 
Offset. Min and Max refer to the minimum and maximum values specifed for the range. 
Particular characteristics to be noted when configuring 
Refer to the help on analog block parameters in the Analog value processing (Page 286)