Troubleshooting Chart 6
RUNS FOR 25-50 SECONDS, 
THEN TURNS OFF.
CHECK FIRING RATE OF UNIT.
IS UNIT FIRING AT THE CORRECT RATE?
NO
DOES THE UNIT USE LP GAS.
YES
NO
CHECK GAS ORFICICE SIZE.
IS GAS ORIFICE SIZE CORRECT.
CHECK REPAIR PARTS LIST 
FOR CORRECT SIZE. IS GAS ORIFICE 
CLEAR OF BLOCKAGE.
ADJUST RATE AS DESCRIBED IN THE 
CHECK OUT PROCEDURE AND 
ADJUSTMENT SECTION
OF THE MANUAL.
CHART 5
NO #2
YES
CHECK BURNER FOR ANY DETERIORATION 
IN THE FLAME PORTS. ARE BURNER PORTS 
IN GOOD CONDITION.
NO
REPLACE WITH CORRECT 
AIR BAFFLE.
YES
CHECK FLAME SIGNAL > 0.6uA?
CONSULT BOILER MFGR. FOR 
SPECIFIC INSTRUCTIONS. REQUIRES 
SPECIFIC TOOLS.
NO
YES
REPLACE BURNER
REPLACE IBC
BOILER SHUTS OFF BEFORE END OF 
CALL FOR HEAT. ARE HI LIMIT 
AQUASTAT CONTACTS CLOSED?
NO
BOILER OFF ON HIGH LIMIT. IS 
ACTUAL BOILER WATER TEMP.
GREATER THAN HI LIMIT SET POINT 
MINUS 30°F CONTROL DIFFERENTIAL?
NO
NO
REPLACE
AQUASTAT
OK
YES
SEE TROUBLESHOOTING PATH 
#2 ABOVE
CHART 5
NO #3
CHART 5
YES
SET THERMOSTAT BELOW ROOM 
TEMPERATURE TO END CALL FOR 
HEAT
DOES CIRCULATOR PUMP STOP?
NO
ARE THERMOSTAT CONTACTS OPEN?
REPLACE THERMOSTAT
NO
YES
REPLACE IBC
YES
VALE LIGHT IS OFF
REMOVE WIRING HARNESS 
CONNECTION CN9 FROM GAS 
CONTROL DOES GAS CONTROL 
CLOSE?
NO
REPLACE GAS CONTROL
NO
YES
YES
DOES DRAFT BLOWER 
STOP AFTER 30 
SECOND POST PURGE?
NO
REPLACE IBC
YES
YES
SYSTEM OK 
YES
REPLACE GAS CONTROL.
15 - TROUBLESHOOTING