Differential air pressure switch is safety device which 
prevents boiler from firing if there is air intake, boiler heat 
exchanger or vent blockage.
Following steps and diagram indicate location of connection 
points required to measure offset pressure using inclined 
Manometer or Differential pressure gauge. Only one device 
is required to measure offset pressure.
1. 
Turn off service switch, or lower thermostat setting.
2. 
Remove vinyl caps from Tee.
3. 
Install testing lines as shown to inclined manometer or 
differential pressure gauge with ability to read 0.01” to 
at least 6.0” w.c.
4. 
Turn on service switch and set thermostat to call for 
heat.
5. 
If manometer readings do not correspond to Table 11 
check for possible causes:
•  Blockage or moisture in suction lines to switch.
•  Blockage or moisture in orifice installed in suction 
lines to switch.
•  Blockage in air intake or vent pipes.
•  Undersized air intake or vent pipes.
•  Loose blower wheel on motor shaft.
•  Incorrect pressure switch or pressure switch set-
point.
•  Gas valve out of adjustment.
6. 
When pressure reading corresponds to Table 11 
and pressure switch is operating properly, remove 
testing lines and reinstall vinyl caps to tee and 3-way 
connector.
Table 11  - Correct Manometer Readings
Boiler Status
Differential Pressure
Switch  Contacts
Not Running 
0”
3.5”
Closed
0.5”
Open
Running
 Without 
Blockage 
(Approximate 
minimum vent 
lengths)
1.00” for Model 125
3.5”
0.5”
Closed
Closed
1.50” for Model 150
1.50” for Model 175
2.00” for Model 200
Running With 
Blockage
Greater Than or Equal 
To Setpoints
3.5”
Open
0.5”
Closed
Figure 22 - Locations Of Connection Points 
Required To Check Differential Air 
Pressure
Differential Air Pressure Switch Check
15 - TROUBLESHOOTING