HP Performance Optimized Data Center (POD) 40c 빠른 설정 가이드
Supported facility connections 20
Humidifier
A dedicated water supply and approved drainage is required for the humidifier. For more information about
the humidifier, see the HP Performance Optimized Datacenter 40c G2 Operation and Maintenance Manual
the humidifier, see the HP Performance Optimized Datacenter 40c G2 Operation and Maintenance Manual
provided with the HP POD 40c G2.
The following image shows the location of the humidifier drain and water supply.
End view shown
The following image shows the location of the humidifier drain and water supply.
End view shown
IMPORTANT:
Confirm with the AHJ that condensate water and rain water can be mixed in the
same drainage.
HP POD 40c G2 security
The HP POD 40c G2 is equipped with standard key lock hardware for each personnel entry door and
external electrical cabinet. Each personnel entry door includes a door access contact that can be connected
to the customer facility security system.
Additional options for controlled access security include the following:
to the customer facility security system.
Additional options for controlled access security include the following:
•
Electronic card reader
•
12-digit security code keypad
•
Magnetic lock on each personnel entry door and dynamic hot aisle door
Fire, safety, and security notifications
Dry contacts are provided to enable the connection between the HP POD 40c G2 fire alarm system and the
customer facility fire system. If the HP POD 40c G2 is connected to the customer facility systems, then the
alarms initiated by the HP POD 40c G2 notify the facility systems.