HP Performance Optimized Data Center (POD) 40c Guia De Configuração Rápida

Página de 41
 
Supported facility connections  20 
Humidifier 
A dedicated water supply and approved drainage is required for the humidifier. For more information about 
the humidifier, see the HP Performance Optimized Datacenter 40c G2 Operation and Maintenance Manual 
provided with the HP POD 40c G2. 
The following image shows the location of the humidifier drain and water supply. 
End view shown 
 
  
 
IMPORTANT:
  Confirm with the AHJ that condensate water and rain water can be mixed in the 
same drainage. 
  
 
HP POD 40c G2 security 
The HP POD 40c G2 is equipped with standard key lock hardware for each personnel entry door and 
external electrical cabinet. Each personnel entry door includes a door access contact that can be connected 
to the customer facility security system. 
Additional options for controlled access security include the following: 
 
Electronic card reader 
 
12-digit security code keypad 
 
Magnetic lock on each personnel entry door and dynamic hot aisle door 
 
Fire, safety, and security notifications 
Dry contacts are provided to enable the connection between the HP POD 40c G2 fire alarm system and the 
customer facility fire system. If the HP POD 40c G2 is connected to the customer facility systems, then the 
alarms initiated by the HP POD 40c G2 notify the facility systems.