Increasing the plant availability
For the individual telecontrol protocols, reference was already 
made as to how the availability of telecontrol communication 
can be increased using redundant transmission paths. How-
ever, as a result of seamless integration of the telecontrol 
technology into the SIMATIC PCS 7 process control system, the 
redundant design of the telecontrol communication is embed-
ded in the redundancy concept of the complete system and 
must therefore be considered globally. 
The example of a SIMATIC PCS 7 process control system 
with integral telecontrol linking of RTUs on the basis of 
the IEC 870-5-101/IEC 870-5-104 protocols demonstrates the 
various possibilities for increasing plant availability:
• Redundant SIMATIC PCS 7 TeleControl OS servers for pro-
cess control of central and widely distributed units and for 
archiving
• Redundant system bus for system communication
• Redundant telecontrol communication between control 
center and RTUs over two separate transmission paths 
• Redundant RTUs on the basis of S7-400H/ S7-400FH con-
trollers for local automation of remote units
• Redundant PROFIBUS for communication between control-
ler and process I/O (I/O modules, process instruments and 
devices in the field)
• Redundant process I/O
It is also possible to implement safety-related functions in 
the RTU (up to SIL 3) based on the S7-400FH controller and 
F modules in the ET 200M remote I/O station.
Redundant telecontrol configuration based on the 
IEC 870-5-101/IEC 870-5-104 protocols
G_PCS7_XX_00274
SIMATIC PCS 7 
OS clients
Control center 
SIMATIC PCS 7 
TeleControl OS
with redundant 
servers
Redundant system bus
Terminal bus
IEC 870-5-101 
redundant
IEC 870-5-104 
redundant
TCP/IP to serial 
converter
RTU S7-400H
RTU 
S7-400H 
with CP 443
TCP/IP 
WAN router
ET 200M
redundant
ET 200M redundant 
with 2 x CP 341