Siemens 125-5050 사용자 설명서

다운로드
페이지 38
Chapter 1 – Product Overview 
12 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
Communication Wiring 
 
The controller connects to the field panel by means of a Floor Level Network (FLN) 
trunk. Communication wiring connects to the three screw terminals on the controller 
labeled “+” (positive), “-“(negative), and “S” (Shield). See the following figure. 
 
 
Controller LED Indicators 
The controller has six Light Emitting Diode (LED) indicators (see the figure 
Siemens 
BACnet ATEC). 
 
Controller LEDs. 
LED Type 
Label  
(if present)* 
LED 
Number 
Indication 
DO 
LED 3 - LED 5 
3 - 5 
Indicates the ON/OFF status of the DO 
associated with it. A glowing LED indicates 
that the DO is energized. 
Transmit 
TX 
Indicates, when flashing, that the controller is 
transmitting information to the field panel. 
Receive 
RX 
Indicates, when flashing, that the controller is 
receiving information from the field panel. 
BST 
”Basic Sanity 
Test” 
BST 
Indicates, when flashing ON and OFF once 
per second, that the controller is functioning 
properly. 
 
* Some LED labels and numerals may be hidden by the controller cover. 
See also