Chapter 2 – Applications 
14 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
Chapter 2 – Applications 
Basic Operation 
The BACnet ATEC provides Direct Digital Control (DDC) for Variable Air Volume (VAV) 
terminal box applications. Temperature control varies with the application. If present, 
heating can be provided by hot water, up to three stages of electric reheat, or optional 
baseboard radiation. 
Sequencing Logic (optional) 
This application has the additional capability to sequence the flow and mechanical 
heating when heated supply air is available. 
Control Temperature Setpoints 
The controller maintains a specified temperature setpoint based on Day/Night mode, or 
the heating/cooling mode, or the setpoint dial (if used). 
Day/Night Mode 
The controller maintains the specified day setpoint temperature during daytime hours 
and the specified night setpoint at night. 
Night Mode Override Switch 
If the ROOM TEMPERATURE SENSOR has an override switch, it can be used to 
command the controller into day mode for an adjustable period of time. This only 
affects a controller in night mode. 
Control Loops 
Temperature Loop – Heating Loop – Cooling Loop 
Maintain temperature setpoint by changing the flow setpoint or modulating the heat 
source (valve/electric heat). 
Flow Loop 
Maintains flow setpoint by modulating the damper actuator.