Chapter 2 – Applications 
21 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
See the following figure.   
 
Fan Operation 
 
The fan turns on when heating is required. 
[insert TEC2566CD] 
Application 2867 VAV Parallel Fan Powered with Hot Water Reheat 
In Application 2867, the controller modulates the supply air damper of the terminal box 
for cooling and modulates a hot water valve for heating. When in heating, the terminal 
box either maintains minimum airflow or modulates the supply air damper. Application 
2867 has a parallel fan that re-circulates the room air. In order for the terminal box to 
work properly, the central air-handling unit must provide supply air. 
See the following figure.