Chapter 2 – Applications 
19 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
 
Application 2864 VAV Series Fan Powered with Electric Reheat 
In Application 2864, the controller modulates the supply air damper of the terminal box 
for cooling and controls stages of electric reheat for heating. When in heating, the 
terminal box either maintains minimum airflow or modulates the supply air damper. 
Application 2864 has a series fan for air circulation. In order for the terminal box to 
work properly, the central air-handling unit must provide supply air. 
See the following figure.  
 
Fan Operation 
 
 
 
CAUTION 
On series fan powered terminal boxes, the terminal box fan must be 
controlled/interlocked to start either before or at the same time as the central air 
handler. Failure to do so may cause the terminal box fan to rotate backwards and 
cause consequent damage at start up. 
  
In day mode, the fan is ON all the time. In night mode, the fan cycles on when heating 
or cooling is required.