Chapter 13 - Troubleshooting 
  
Graphics Issues
175
Siemens Industry, Inc. 
 
125-3584T
 
 
panels lose communication, an error message will display for each panel, indicating 
which panel has lost communication. 
If an FPWeb-enabled panel loses communication, the Device Failures Count will 
increase, and the Panel will have an associated triangle icon in the navigation pane 
instead of an arrow. 
Solution: Check connections. Verify the panel is still FPWeb-enabled. Communications 
should be reestablished automatically as long as the browser session has not been 
terminated. 
Graphics Issues 
Displaying New Graphics in Browser 
Issue: The Web browser displays an older graphics file, even after the file has been 
modified and saved.  
Solution: Internet Explorer and Firefox store Web pages and flash files as “temporary 
Internet files” for faster loading. Clear the cache by deleting temporary Internet files 
(see browser Help system for more information). This should allow the application to 
display the newest graphics files. 
Existing Images are Resized after New Animation Frames are Added 
Issue: After a new animation image has been added to the set of frames in FINlite’s 
Animation Editor window, existing images are automatically resized to match the frame 
added by the user. 
Solution: Before bringing them into FINlite, be sure the images to be added for editing 
animation are sized similarly to the existing images, to avoid automatic resizing issues. 
User is Unable to Log in to Panel via FINlite 
Issue: If you open a graphic from your local file system before you have logged into 
any panels and then select Enter Live Mode, FINlite will display an error message. 
When you click OK, the login screen will display. The Panel Address will be populated 
with the last address that was used for login. If this is the first login of the current 
FINlite session, then the URL of the first bound point in the graphic is used. The Panel 
Address field is grayed out. If this is not the desired panel or if this panel is currently 
failed or unavailable, you cannot change to a different panel address.  
Solution: Cancel the login by selecting the X in the corner of the error window. Click 
Connect To Panels and login to one of the existing panels. 
Graphics Files do not Save Properly 
Issue: When using some special characters in graphics file names, the files do not 
save to the panel properly. 
Solution: You cannot create files which will be saved to the A:\ or B:\ drives that contain 
any of the following: 
  The following special characters:  
. \ / : * ? “ < > | (includes period) 
  Characters with accent marks (such as é or ô)