Chapter 5 - Point Commander 
Using the Point Commander Application 
40 
Siemens Industry, Inc. 
 
125-3584T
 
 
Steps for Commanding Point Values 
1.  Access the Commanding window through the Devices/Points bar in the navigation 
pane on the left side of the screen.  
2.  Drill down to the desired point.  
3.  Double-click the point name (or single-click the command icon to the right of the 
point name) to open the basic (default) Commanding window. 
4.  For points that have priority array, toggle between the Basic and Advanced 
command options using the Advanced/Basic button at the bottom of the 
Commander window. 
5.  Make the necessary changes in the Commander window. For more information 
about the fields available in the Commander window, see the 
User Interface 
Descriptions for Point Commander
 section. 
6.  Click Command to initiate the changes and begin controlling the point with the new 
settings.  
NOTE: It is not necessary to check or uncheck the Out of Service check box in a 
separate step. 
  The status of the command displays in the Feedback field. 
This procedure is now complete. Close the Commander window by using the X in the 
top right corner of the window. 
  
 
 
CAUTION 
Release All Commanded Points
Remember to eventually release all commanded points to NULL priority so that the 
system is automatically controlled.  
In the Current Value field on the Basic or Advanced Commander window, type N. NULL 
will be auto-filled into the field.  
Failure to release commanded points may lead to unexpected results.  
  
Disabling and Re-enabling a Point (Out-of-Service) 
Disabling a point means using the Point Commander to manually change a point status 
to Out-of-Service. Point priority does not change, and the value state cannot be 
changed by an interface terminal or PPCL statement until the point is re-enabled. 
When a point is disabled, the point status displays *O* on point logs and displays. This 
procedure is normally used to validate control sequences and troubleshoot equipment. 
 
This procedure is only available to users with Command or higher access to points.
Steps for Disabling/Re-enabling a Point 
1.  Access the Commanding window through the Devices/Points bar in the navigation 
pane on the left side of the screen.