Chapter 5 - Point Commander 
Using the Point Commander Application 
42 
Siemens Industry, Inc. 
 
125-3584T
 
 
In the advanced Commanding window, the point priority can be changed in the Priority 
drop-down field. The value of the point can be changed in the current highest priority 
field.  
1.  Click the drop-down arrow in the Priority field to choose the priority.  
2.  Click the arrows in the current highest priority field OR in the Present Value field to 
change the point value in the highest priority. 
3.  Click Command to initiate the change. The status of the command displays in the 
Feedback field. 
  When the point value is changed in the current highest priority field, the value 
will be reflected in the Present Value field once the change is initiated, and vice 
versa. 
This procedure is now complete. Close the Commanding window by clicking the X in 
the top right corner of the window. 
  
 
 
CAUTION 
Release All Commanded Points
Remember to eventually release all commanded points to NULL priority so that the 
system is automatically controlled.  
In the Current Value field on the Basic or Advanced Commander window, type N. NULL 
will be auto-filled into the field.  
Failure to release commanded points may lead to unexpected results.