Siemens Building Technologies Field Panel Web Server 125-3584T 사용자 설명서

다운로드
페이지 177
Chapter 10 - Create/Edit 
  
Event Enrollment
93
Siemens Industry, Inc. 
 
125-3584T
 
 
Event Enrollment 
 
For information about intrinsic alarming, see the 
Point Editor
 section of this document.
 
 
To receive alarms from BTECs and PPMs, Event Enrollment must be used.
 
Section Overview 
This section discusses the following topics: 
  Event Enrollment Editor Overview 
–  User Interface Description for the Event Enrollment Editor 
–  Tips for Using the Event Enrollment Editor 
  Event Enrollment Editor Step-by-Step Instructions 
–  Creating an Event Enrollment Object 
–  Modifying an Event Enrollment Object 
–  Viewing an Event Enrollment Object 
–  Deleting an Event Enrollment Object 
–  Alarm Reports 
Event Enrollment Overview 
Event Enrollment objects are stand-alone alarm objects which change their status 
based on the condition of another object. The purpose of an event enrollment object is 
to identify an event (for example, exceeding of an alarm level) and to provide a 
connection between the event occurrence and the transmission of notification 
messages to one or more recipients. 
User Interface Description for the Event Enrollment Editor 
The Event Enrollment Editor can be accessed via the Create/Edit bar in the navigation 
pane on the left side of the screen.  
1.  Click the Event Enrollment icon.  
  The Event Editor window will display. 
2.  In the Event Editor, choose the desired panel, and click the existing Event 
Enrollment Object name to open the viewing area in the right pane of the Event 
Editor (a COS type Event Enrollment Object is shown):