  The Object Name field allows you to name the Event Enrollment Object using up to 
30 characters. This field is required for creating an Event Enrollment Object and 
cannot be edited in an existing object. 
  The Object Identifier field displays the point Object Identifier information. An Object 
Identifier consists of an object type and instance number. The object type is the 
BACnet standard object type enumeration value (Event Enrollment object type 
enumeration value is 9). You can enter an instance number on point creation in this 
field, or leave it blank. If you do not enter an instance number in the Object 
Identifier field on creation, the controller will automatically enter the next available 
instance number. After creation, the Object Identifier field cannot be edited and the 
field will show the object type and instance number separated by commas. 
  The Description field allows you to describe the Event Enrollment Object using up 
to 16 alphanumeric characters. This field is optional for creating an Event 
Enrollment Object and can be edited. 
  The event type options allow you to choose the Event Enrollment Object type: 
–  COS - Change of State (for BI, BV, MI, and MV point types) 
–  FAL - Command Failure (for BO and MO point types) 
–  LIM - Floating Limit (for AO and AV point types) 
–  OOR - Out of Range (for AI, AO, and AV point types) 
  The OFFNORMAL, NORMAL, and FAULT Alarm Enabled checkboxes allow you to 
define which transitions will be reported. These parameters are optional for Event 
Enrollment Object creation and can be edited. 
  The Notify Type dropdown allows you to choose “alarm” or “event” type of 
notification. 
  The Reference Point field allows you to choose the object reference for the object 
to be monitored. This parameter is required for Event Enrollment Object creation 
and cannot be edited.