Functions 
 
3.9 Communication 
 
M200D AS-Interface Basic 
40
 
Manual, 03/2009, A5E01668085-01 
●  If no motor ON command is present, a group alarm is output. 
The alarm is canceled when motor protection is reactivated. 
●  If a motor ON command is present, a group fault is output immediately and a 
corresponding internal shutdown command generated, which must be acknowledged with 
"trip reset". 
–  If the motor ON command remains, the fault can only be acknowledged with "trip 
reset" once the fault has been rectified (activate at least one motor protection 
function). 
–  If the motor ON command is reset, the group fault can be "downgraded" to a group 
alarm even if a setting is incorrect. 
3.9.3 
Message output 
 
Message 
Meaning 
Output via 
General messages   
Ready (automatic) 
• 
Device can be controlled via BUS 
• 
Automatic mode 
• 
No fault 
Process image of inputs 
Group fault 
At least one fault is set. 
• 
LED 
• 
Diagnostics via parameter 
channel 
Group alarm 
At least one alarm is present. 
• 
LED 
• 
Diagnostics via parameter 
channel 
Mode monitoring 
Manual operation 
local mode  
Manual operation via integrated 
manual local control or via the local 
device interface (hand-held device) 
Diagnostics via parameter channel