Functions 
 
3.10 Trip reset 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
41
 
3.10 
Trip reset 
Trip reset acknowledges all the faults that are currently present in the starter and that can be 
acknowledged. A fault can be acknowledged if its cause has been rectified or if it is no longer 
present.   
The trip reset can be triggered by: 
●  Remote reset via the bus interface (DO 0 CW ON and DO 1 CCW ON simultaneously) 
●  Local reset via the key-operated switch (0 position; order option) 
●  Local reset via the device interface (hand-held device) 
 
3.11 
Self-test 
Description  
Two types of self-test can be carried out: 
●  Self-test at startup 
This is automatically selected when the device is switched on or initialized. 
●  Self-test during operation: 
The motor starter monitors (cyclically) specific device components and signals any faults 
(device faults). 
Self-test fault 
If a fault occurs, the "DEVICE" LED lights up red. The fault can only be acknowledged by 
switching the device off and then on again. If the fault is still present, the self-test will return a 
fault again when the device is switched on. In this case, the motor starter must be replaced. 
 
 
Note 
Specific device components are monitored continuously (internally) by the motor starter and 
the results signaled with the message "Device fault".