Installation / connection 
 
4.2 Connection 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
57
 
Consumer connection on the motor starter 
For the assignment of X2, see Power terminal (Page 58): 
●  A flexible Cu cable with 1.5 mm
2
 or 2.5 mm
2
 
–  Without brake control: 3 wire + PE 
–  With brake control: 5 wire + PE 
–  With temperature sensor: 2 additional wires 
–  Han Q8/0 pin power connector 
 
Item 
Order no. 
Connector set, 8 X 1.5 mm
2
, 9 pin, complete with PG16 cable entry 
3RK1902-0CE00 
Connector set, 8 X 2.5 mm
2
, 9 pin, complete with PG16 cable entry 
3RK1902-0CC00 
4.2.3 
Installing and wiring power connectors 
 
DANGER 
 
Hazardous voltage 
Can Cause Death, Serious Injury, or Property Damage 
Before starting work, disconnect the system and devices from the power supply. 
 
Installa and wire the power connectors as follows:    
 
Step 
Procedure 
Route the cable through the cable gland, sealing insert (enclosed), and the connector housing. The sealing 
insert is available in the following gradings: 
Permissible external diameter of the cable 
Sealing insert 
7.0 to 10.5 mm 
9.0 to 13.0 mm 
11.5 to 15.5 mm 
Green 
Red 
White 
Strip the cable over a length of 20 mm. 
Strip the cores over a length of 8 mm. 
Secure the contact sockets/pins on the cores by crimping or soldering them. 
Sort the contact sockets/pins in the socket/pin insert in accordance with the assignments (see section Power 
terminal (Page 58)). The contact sockets/pins should not engage yet. Make sure that they are correctly 
assigned. Push the contact sockets/pins into the socket/pin insert until they engage. Use a suitable tool to 
remove contact sockets/pins that have already been installed (Han Q4/2: 3RK1902-0AB00, Han Q8/0: 
3RK1902-0AJ00. 
Make sure that the position of the coding is correct, pull the cable back, and secure the socket/pin insert in the 
connector housing using the cross-recessed screws enclosed. 
Secure the cable gland. When doing so, make sure that the cable is not twisted against the connector housing.