Technical specifications 
8
8.1 
General technical specifications 
 
Location   
In the plant 
Wall mounted (near motor) 
Permissible mounting 
positions 
 
Vertical, horizontal, flat 
Degree of protection 
IP65 
Waterproof to IEC 529 (DIN 40050) 
Protection class 
IEC 60364-4-41 (DIN VDE 0100-410) 
Touch protection 
Finger-safe 
Degree of pollution 
To IEC 60664  
Cooling 
Convection 
No additional cooling required 
Operating temperature 
–25°C to + 40°C 
max. 55°C 
 
With reduction of I
(see "Derating") 
Transport and storage 
temperature 
–40°C to + 70°C 
— 
Air humidity 
10 % to 95 % 
Condensation must not be allowed to form 
Max. temperature change 
1 K / min 
IEC 60068, Part 2-14 
Chemical environment 
conditions 
3C3 
conforming to IEC 60721-3-3 
Installation altitude 
1000 m 
2000 m 
No restrictions 
With restrictions (reduction of I
e
 by 1 % every 
100 m up to 2000 m) 
Vibration resistance 
2 g  
To IEC 60 068, Part 2-6 
Shock 
12 g with 11 ms 
without influencing point of contact: 
9.8 g / 5 ms or 5.9 g / 10 ms 
To IEC 60 068, Part 2-27 
half-sine 
Free fall 
0.6 m 
In product packaging 
ESD 
8 kV air discharge 
4 kV contact discharge 
IEC 61000-4-2 
Severity grade 3 
Electromagnetic fields 
10 V/m 
IEC 61000-4-3 
Severity grade 3 
BURST 
2 kV / 5 kHz supply voltage 
2 kV / 5 kHz data cables 
2 kV / 5 kHz process cables 
IEC 61000-4-4 
Severity grade 3 
SURGE  
Installation class 1 to 3 
1)
 
1 / 2 kV  
IEC 61000-4-5  
Severity grade 3  
Emitted interference 
Limit value class A 
EN 55011 
1)
  If the starter is used in installation class 3 (increased overvoltage due to parallel cable installation), an overvoltage 
protection module (3RK1901-1GA00 and 3RG9030-0AA00) must be used.