Technical specifications 
 
8.3 Brake control 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
91
 
Motor starter version   
DSte / RSte 
sDSte / sRSte 
Isolation stability 
Rated surge capacity U
imp
 
6 kV 
Rated insulation voltage U
i
 
500 V 
Safe isolation between main and control circuits  
to IEC60947-1 Appendix N 
400 V 
Short-circuit protection 
Instantaneous overcurrent release 
 - I
e max
 = 2 A 
 - I
e max 
= 9 / 12 A 
 
26 A  
208 A 
Rated ultimate short-circuit breaking capacity I
q
 at 400 V  
50 kA  
 
 
 
Note 
To change the direction of rotation, a mechanically-switching reversing contactor is 
integrated in reversing starters with solid-state switching. The preferred position of this 
contactor is "CW rotation". When the direction is changed to CCW rotation, the reversing 
contactor is activated and, after a 150 ms delay, the electronic contacts. This delay is only 
relevant (active) whenever the direction of rotation is changed.  
After 1 hour (implemented time: 65 min) without a "CCW ON" command, the reversing 
contactor automatically reverts to its preferred position (CW rotation). 
 
 
8.3 
Brake control 
 
Brake version   
400 V AC / 230 V  
180 V DC 
Rated operating voltage 
400 V AC 
180 V DC 
Continuous current 
< 0.5 A 
< 0.8 A 
Inrush current at t < 120 ms 
< 5 A 
< 5 A 
Switching capacity to IEC60947-5-1 
 - AC 15, at 400 V AC 
 - DC 13, at 180 V DC 
 
0.4 A 
-  
 
0.8 A 
Fault message with non-controlled brake 
No 
Protective measures 
Short-circuit protection 
Yes, 1 A melting fuse 
 
Inductive interference protection 