4.4 ERROR
HANDLING
The meter can detect errors in either the test or the measurement modes. When in the measurement
mode, a blinking vertical bar will appear in the top left corner of the display indicating an error has
been detected. If the error reporting function is enabled, error messages will be displayed as separate
menu pages. The fi rst line of the error menu page indicates the total number of errors and the second
line displays the error message. Measurement mode error messages are listed below.
Error Message
(display second line)
Type Description
Corrective Action
Required
NO SIGNAL
No signal from the vortex
sensor
sensor
No fl ow. Also check for any other errors dur-
ing power-on diagnostics. If there is a sensor
problem, contact ONICON.
ing power-on diagnostics. If there is a sensor
problem, contact ONICON.
LOW FREQ.
Vortex frequency is too low
Check for fl ow rate lower than specifi ed mini-
mum. Contact ONICON.
mum. Contact ONICON.
HIGH FREQ.
Vortex frequency is too high
Check for fl ow rate higher than specifi ed maxi-
mum. Contact ONICON.
mum. Contact ONICON.
LOW FLOW
Flow rate lower than speci-
fi ed range
fi ed range
Converter will continue to display actual fl ow
rate. However, accuracy of measurement may
suffer.
rate. However, accuracy of measurement may
suffer.
HIGH FLOW
Actual fl ow rate higher than
specifi ed range
specifi ed range
Corrective action depends on application pro-
cess. If the fl ow rate exceeds the maximum
value it may damage the sensor physically.
cess. If the fl ow rate exceeds the maximum
value it may damage the sensor physically.
INV. CONFIG.
Confi guration data in non-
volatile memory is not valid
volatile memory is not valid
Contact ONICON.
ISO FAIL
Checked
during
power-
on only
Sensor isolation has failed
Contact ONICON.
AMP FAIL
Pre-amplifi er section has
failed
failed
Contact ONICON.
PIEZO FAIL
Piezo wires broken
Contact ONICON.
CHECK INST
Flow signal quality is bad
Check: 1) Flow rate, if OK; 2) Check for
excessive pipe vibration and upstream fl ow
disturbances; 3) Contact ONICON.
excessive pipe vibration and upstream fl ow
disturbances; 3) Contact ONICON.
LOW SIGNAL
Vortex signal amplitude too
low
low
Check: 1) Flow rate, if OK; 2) Contact ONI-
CON.
CON.
HIGH SIGNAL
Vortex sensor signal
amplitude too high
amplitude too high
This occurs in cases of high density medium.
Check 1) Flow rate, if OK 2) Contact ONI-
CON.
Check 1) Flow rate, if OK 2) Contact ONI-
CON.
LOW.TEMP.PHY.
Operating temperature is
lower than the physical limit
lower than the physical limit
Take corrective action depending on the pro-
cess.
cess.
HIGH.TEMP.PHY.
Operating temperature is
higher than the physical limit
higher than the physical limit
Take corrective action immediately. This will
cause damage to the shedder bar as well as
to the electronics.
cause damage to the shedder bar as well as
to the electronics.
T.SENS.SHORT
Temperature sensor/wires
short circuit
short circuit
Indicates a fault in the temperature sensor.
Contact ONICON.
Contact ONICON.
T.SENS.OPEN
Temperature sensor open
circuit
circuit