F-2200 Series Vortex Flow Meter Installation and Operation Guide • Revised 12/08
20 
4.4 ERROR 
HANDLING
 
The meter can detect errors in either the test or the measurement modes. When in the measurement 
 
mode, a blinking vertical bar will appear in the top left corner of the display indicating an error has 
 
been detected. If the error reporting function is enabled, error messages will be displayed as separate 
 
menu pages. The fi rst line of the error menu page indicates the total number of errors and the second 
 
line displays the error message. Measurement mode error messages are listed below. 
Error Message 
(display second line)
Type Description
Corrective Action 
Required
NO SIGNAL
No signal from the vortex 
sensor
No fl ow. Also check for any other errors dur-
ing power-on diagnostics. If there is a sensor 
problem, contact ONICON.
LOW FREQ.
Vortex frequency is too low
Check for fl ow rate lower than specifi ed mini-
mum. Contact ONICON.
HIGH FREQ.
Vortex frequency is too high
Check for fl ow rate higher than specifi ed maxi-
mum. Contact ONICON.
LOW FLOW
Flow rate lower than speci-
fi ed range
Converter will continue to display actual fl ow 
rate. However, accuracy of measurement may 
suffer.
HIGH FLOW
Actual fl ow rate higher than 
specifi ed range
Corrective action depends on application pro-
cess. If the fl ow rate exceeds the maximum 
value it may damage the sensor physically.
INV. CONFIG.
Confi guration data in non-
volatile memory is not valid
Contact ONICON.
ISO FAIL
Checked 
during 
power-
on only
Sensor isolation has failed
Contact ONICON.
AMP FAIL
Pre-amplifi er section has 
failed
Contact ONICON.
PIEZO FAIL
Piezo wires broken
Contact ONICON.
CHECK INST
Flow signal quality is bad
Check: 1) Flow rate, if OK; 2) Check for 
excessive pipe vibration and upstream fl ow 
disturbances; 3) Contact ONICON.
LOW SIGNAL
Vortex signal amplitude too 
low
Check: 1) Flow rate, if OK; 2) Contact ONI-
CON.
HIGH SIGNAL
Vortex sensor signal 
amplitude too high
This occurs in cases of high density medium. 
Check 1) Flow rate, if OK 2) Contact ONI-
CON.
LOW.TEMP.PHY.
Operating temperature is 
lower than the physical limit
Take corrective action depending on the pro-
cess.
HIGH.TEMP.PHY.
Operating temperature is 
higher than the physical limit
Take corrective action immediately. This will 
cause damage to the shedder bar as well as 
to the electronics.
T.SENS.SHORT
Temperature sensor/wires 
short circuit
Indicates a fault in the temperature sensor. 
Contact ONICON.
T.SENS.OPEN
Temperature sensor open 
circuit